Troubleshooting

Resolving InstaStart™ Ignition Performance Issues

If you are having difficulty with your BBQ’s Electronic Ignition a quick visual inspection of the following
will help to identify the cause:

  1. Check the electronic ignition box and InstaStart™ button for un-plugged electrode wires. Push-in firmly.
  2. Check wires for damage.
  3. Replace the battery in the electronic ignition box. Positive end facing outwards.
  4. Check battery cap for proper threading
  5. Check that all electrodes (attached to the burners) spark when the Instastart™ button is pressed.
  6. Check to make sure that the Instastart™ ignition button, located on the left side shelf fascia, has continuous clicking sound when pressed
  7. Check to ensure that the tip of the electrode is positioned close enough to the burner port holes to light correctly.
  8. Check electrodes for cracks in the porcelain insulator.

Replace the battery. Open the Lid.
Press Ignition button and listen for rapid clicks.

Coleman® Even Heat™ Small Spaces

Coleman Even Heat Barbecue 2 Burner Ignition Diagram

Coleman® Revolution™ 3-BURNER / 4-BURNER

Coleman Revolution 3 Burner / 4 Burner Ignition Diagram

Burners Troubleshooting

Problem Identifying the cause
Burner will not light
(with igniter or match)
  1. Low or out of propane
  2. Cylinder or the gas supply valve is turned off
  3. Positive connection has NOT been made between the tank and the regulator. Regulator will not allow fuel in the line.
  4. The Flow Limiting Device in the regulator has been activated
  5. Manifold valve assembly is damaged
Fire at control knob and control panel = Flash Fire
  1. Burner port holes and/or Venturi tubes are blocked
  2. Burner is improperly seated on valve gas jet
Yellow smoky flames
  1. Blocked Venturi tubes
  2. Excess cooking salts on burner
Flame blows out on LOW
  1. Flow Limiting Device has been activated
  2. High Wind condition – Adjust the placement of Barbecue to shield from wind
  3. Propane is running low
  4. Burner improperly seated on valve gas jet
  5. Heat Distribution plates are not in position
  6. NATURAL GAS MODELS: Installation issues related to incorrect size supply line installed and /or Water Column supply is not adequate for a Barbecue BTU rating of this grill. Do not use a longer Natural Gas hose than is supplied with your grill.
Burner does not get hot enough
  1. Barbecue needs to be preheated for 5 to 10 minutes with a closed lid. Outside temperatures will affect the amount of preheat time required.
  2. Flow limiting device in regulator has been activated and requires resetting
  3. NATURAL GAS MODELS: Installation issues related to incorrect size supply line installed and /or Water Column supply is not adequate for a Barbecue BTU rating of this grill. Do not use a longer Natural Gas hose than is supplied with your grill.
Low or incomplete flame (assuming burners and Venturi tubes are free and clear of blockages)
  1. Proper start up and shut down procedure not followed
  2. Flow limiting device in regulator has been activated and requires resetting
  3. Flame Tamers (heat plates) are missing or not in position
  4. NATURAL GAS MODELS: Installation issues related to incorrect size supply line installed and /or Water Column supply is not adequate for a Barbecue BTU rating of this grill. Do not use a longer Natural Gas hose than is supplied with your grill.
Too much heat/ Excessive flare up
  1. Excessive fat in meat
  2. Grease drain plugged
  3. Cooking system including flame tamers and cooking grates have a build up of grease that must be removed
  4. Lower casting of the Barbecue is clogged with grease
  5. Cooking on lower temperature setting. Reduce temperatures according to type of foods being cooked.